DIN 2401 - page 2 - excerpt |
material of the pressure component | operating temperature °C ³) | PN 6 DN 15-200 | PN 16 DN 15-500 | PN 25 DN 15-500 | PN 40 DN 15-500 |
---|---|---|---|---|---|
permissible operating pressure ¹) bar | |||||
GG 25 (cast iron 25) / EN-GJL-250 / EN-JL 1040 | 20 | 6 | 16 | ||
200 | 5 | 13 | |||
300 | 5 | 13 | |||
GGG 40 ⁴) / (cast iron 40) / EN-GJS-400-15 / EN-JS 1030 | 20 | 16 | 25 | ||
200 | 13 | 20 | |||
300 | 13 | 16 | |||
350 | 10 ²) | 15 ²) | |||
GS-C25 ⁴) / (cast steel C25) GP240GH / 1.0619+N | 20 | 25 | 40 | ||
200 | 22 | 35 | |||
300 | 17 | 28 | |||
400 | 13 | 21 | |||
¹) The permissable operating pressure effective for 20° C can be used in the temperature range from -10° C up to +120° C. ²) not included on page 2 of DIN 2401 ³) Valves with innervalves of copper alloys only up to 225° C ⁴) For valves, which shall be applied for over 300° C, expansion screws are required for the flange connection with the pipeline. |